Search for collections on EPrints Repository UNTIRTA

ANALISIS PENEMPATAN PLTS SEBAGAI DISTRIBUTED GENERATION DAN PENAMBAHAN FEEDER DALAM MENGOPTIMALKAN TEGANGAN DAN MENURUNKAN LOSSES PENYULANG PANIMBANG

Arjun Saputra, Paturahman (2025) ANALISIS PENEMPATAN PLTS SEBAGAI DISTRIBUTED GENERATION DAN PENAMBAHAN FEEDER DALAM MENGOPTIMALKAN TEGANGAN DAN MENURUNKAN LOSSES PENYULANG PANIMBANG. S1 thesis, Fakultas Teknik Universitas Sultan Ageng Tirtayasa.

[img] Text (Fulltext)
Arjun Saputra Paturahman_3332210048_Fulltext.pdf
Restricted to Registered users only

Download (6MB)
[img] Text (Bab 1)
Arjun Saputra Paturahman_3332210048_01.pdf
Restricted to Registered users only

Download (4MB)
[img] Text (Bab 2)
Arjun Saputra Paturahman_3332210048_02.pdf
Restricted to Registered users only

Download (719kB)
[img] Text (Bab 3)
Arjun Saputra Paturahman_3332210048_03.pdf
Restricted to Registered users only

Download (932kB)
[img] Text (Bab 4)
Arjun Saputra Paturahman_3332210048_04.pdf
Restricted to Registered users only

Download (1MB)
[img] Text (Bab 5)
Arjun Saputra Paturahman_3332210048_05.pdf
Restricted to Registered users only

Download (235kB)
[img] Text (Daftar Referensi)
Arjun Saputra Paturahman_3332210048_Ref.pdf

Download (232kB)
[img] Text (Lampiran Skripsi)
Arjun Saputra Paturahman_3332210048_Lamp.pdf

Download (2MB)
[img] Text (Cek Plagiasi)
Arjun Saputra Paturahman_3332210048_CP.pdf

Download (19MB)

Abstract

The Panimbang feeder is a power distribution network characterized by high load demands and long transmission lines, which often result in significant voltage drops and power losses. This study aims to analyze two optimization methods: the placement of Solar Power Plants (PLTS) as Distributed Generation (DG) and the addition of feeders, in order to optimize voltage levels and reduce losses on the feeder. Simulations were conducted using the ETAP software based on actual network data from UP3 Banten Selatan. The results show that the strategic placement of four PLTS units at buses 1355, 1204, 1270, and 1337 increased the average voltage to 19.45 kV and reduced losses by up to 76.07%. Meanwhile, the feeder addition method, implemented through parallel networks, increased the average voltage to 19.46 kV and reduced losses by 62.22%. It can be concluded that the Distributed Generation method is more effective in minimizing power losses, while the feeder addition method provides better voltage stability. This research is expected to serve as a reference for the development of more efficient, reliable, and sustainable electrical distribution systems.

Item Type: Thesis (S1)
Contributors:
ContributionContributorsNIP/NIM
Thesis advisorHartono, Hartono197601032002121003
Thesis advisorAdi, Nugraha199507082022031009
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: 03-Fakultas Teknik > 20201-Jurusan Teknik Elektro
Depositing User: Arjun Saputra Paturahman
Date Deposited: 25 Jul 2025 02:34
Last Modified: 25 Jul 2025 02:34
URI: http://eprints.untirta.ac.id/id/eprint/52714

Actions (login required)

View Item View Item