Search for collections on EPrints Repository UNTIRTA

ANALISIS DROP TEGANGAN DAN RUGI-RUGI DAYA PADA JARINGAN TEGANGAN MENENGAH 20 kV PT. PLN UP3 BANTEN UTARA

MEGAWAN, SUKMA (2022) ANALISIS DROP TEGANGAN DAN RUGI-RUGI DAYA PADA JARINGAN TEGANGAN MENENGAH 20 kV PT. PLN UP3 BANTEN UTARA. S1 thesis, UNIVERSITAS SULTAN AGENG TIRTAYASA.

[img] Text (SKRIPSI)
3332160088.pdf
Restricted to Registered users only

Download (4MB)
[img] Text (BAB 1)
SUKMA MEGAWAN_3332160088_01.pdf
Restricted to Registered users only

Download (575kB)
[img] Text (BAB 2)
SUKMA MEGAWAN_3332160088_02.pdf
Restricted to Registered users only

Download (456kB)
[img] Text (BAB 3)
SUKMA MEGAWAN_3332160088_03.pdf
Restricted to Registered users only

Download (224kB)
[img] Text (BAB 4)
SUKMA MEGAWAN_3332160088_04.pdf
Restricted to Registered users only

Download (649kB)
[img] Text (BAB 5)
SUKMA MEGAWAN_3332160088_05.pdf
Restricted to Registered users only

Download (8kB)
[img] Text (DAFTAR PUSTAKA)
SUKMA MEGAWAN_3332160088_REF.pdf
Restricted to Registered users only

Download (145kB)
[img] Text (LAMPIRAN)
SUKMA MEGAWAN_3332160088_LAMP.pdf
Restricted to Registered users only

Download (2MB)

Abstract

Voltage drop can disrupt the load system because the voltage on the receiving side will be lower than on the sending side. At the same time, power losses can harm consumers and electricity supply companies because the power received and the electrical energy sold will be lower. The Polda Serang feeder, Serang City feeder, and Bhayangkara Serang feeder are the three feeders that were studied. The total voltage drop in the existing condition at the Polda Serang feeder is 6.497%, the Serang City feeder is 8.003%, and the Bhayangkara Serang feeder is 3.289%. After repair, the total voltage drop at the Polda Serang feeder decreased to 5.381% and the Serang City feeder decreased to 4.524%.

Item Type: Thesis (S1)
Contributors:
ContributionContributorsNIP/NIM
Thesis advisorSANTOSO, M. IMAN197701302003121007
Thesis advisorPRAMONO, LANTIPUNSPECIFIED
Additional Information: Drop tegangan dapat mengganggu sistem beban karena tegangan yang diterima akan lebih rendah dari tegangan yang dikirim, sedangkan rugi-rugi daya merugikan sisi konsumen dan sisi perusahaan penyediaan listrik karena daya yang diterima dan daya yang terjual akan lebih rendah. Terdapat tiga feeder yang diteliti yakni feeder Polda Serang, feeder Kota Serang, dan feeder Bhayangkara Serang. Total drop tegangan saat kondisi existing pada feeder Polda Serang sebesar 6,497%, feeder Kota Serang sebesar 8,003%, dan feeder Bhayangkara Serang sebesar 3,289%. Setelah dilakukan perbaikan, total drop tegangan pada feeder Polda Serang turun menjadi 5,381% dan feeder Kota Serang turun menjadi 4,524%.
Uncontrolled Keywords: Kata kunci: feeder, drop tegangan, rugi-rugi daya, existing Keywords: feeder, voltage drop, power losses, existing
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: 03-Fakultas Teknik
03-Fakultas Teknik > 20201-Jurusan Teknik Elektro
Depositing User: Mr Sukma Megawan
Date Deposited: 11 Apr 2023 09:42
Last Modified: 11 Apr 2023 09:42
URI: http://eprints.untirta.ac.id/id/eprint/15765

Actions (login required)

View Item View Item